ESP-Modbus
==========
Overview
--------
The Modbus serial communication protocol is de facto standard protocol widely used to connect industrial electronic devices. Modbus allows communication among many devices connected to the same network, for example, a system that measures temperature and humidity and communicates the results to a computer. The Modbus protocol uses several types of data: Holding Registers, Input Registers, Coils (single bit output), Discrete Inputs. Versions of the Modbus protocol exist for serial port and for Ethernet and other protocols that support the Internet protocol suite.
There are many variants of Modbus protocols, some of them are:
* ``Modbus RTU`` — This is used in serial communication and makes use of a compact, binary representation of the data for protocol communication. The RTU format follows the commands/data with a cyclic redundancy check checksum as an error check mechanism to ensure the reliability of data. Modbus RTU is the most common implementation available for Modbus. A Modbus RTU message must be transmitted continuously without inter-character hesitations. Modbus messages are framed (separated) by idle (silent) periods. The RS-485 interface communication is usually used for this type.
* ``Modbus ASCII`` — This is used in serial communication and makes use of ASCII characters for protocol communication. The ASCII format uses a longitudinal redundancy check checksum. Modbus ASCII messages are framed by leading colon (":") and trailing newline (CR/LF).
* ``Modbus TCP/IP or Modbus TCP`` — This is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
Modbus common interface API overview
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
The API functions below provide common functionality to setup Modbus stack for slave and master implementation accordingly. ISP-IDF supports Modbus serial slave and master protocol stacks and provides modbus_controller interface API to interact with user application.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
.. doxygenfunction:: mbc_slave_init
.. doxygenfunction:: mbc_master_init
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
The function initializes the Modbus controller interface and its active context (tasks, RTOS objects and other resources).
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
.. doxygenfunction:: mbc_slave_setup
.. doxygenfunction:: mbc_master_setup
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
The function is used to setup communication parameters of the Modbus stack. See the Modbus controller API documentation for more information.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
:cpp:func:`mbc_slave_set_descriptor`: Initialization of slave descriptor.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
:cpp:func:`mbc_master_set_descriptor`: Initialization of master descriptor.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
The Modbus stack uses parameter description tables (descriptors) for communication. These are different for master and slave implementation of stack and should be assigned by the API call before start of communication.
.. doxygenfunction:: mbc_slave_start
.. doxygenfunction:: mbc_master_start
Modbus controller start function. Starts stack and interface and allows communication.
.. doxygenfunction:: mbc_slave_destroy
.. doxygenfunction:: mbc_master_destroy
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
This function stops Modbus communication stack and destroys controller interface.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
There are some configurable parameters of modbus_controller interface and Modbus stack that can be configured using KConfig values in "Modbus configuration" menu. The most important option in KConfig menu is "Selection of Modbus stack support mode" that allows to select master or slave stack for implementation. See the examples for more information about how to use these API functions.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
Modbus serial slave interface API overview
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
The slave stack requires the user defined structures which represent Modbus parameters accessed by stack. These structures should be prepared by user and be assigned to the modbus_controller interface using :cpp:func:`mbc_slave_set_descriptor()` API call before start of communication.
The interface API functions below are used for Modbus slave application:
.. doxygenfunction:: mbc_slave_set_descriptor
The function initializes Modbus communication descriptors for each type of Modbus register area (Holding Registers, Input Registers, Coils (single bit output), Discrete Inputs). Once areas are initialized and the :cpp:func:`mbc_slave_start()` API is called the Modbus stack can access the data in user data structures by request from master. See the :cpp:type:`mb_register_area_descriptor_t` and example for more information.
.. doxygenfunction:: mbc_slave_check_event
The blocking call to function waits for event specified in the input parameter as event mask. Once master access the parameter and event mask matches the parameter the application task will be unblocked and function will return ESP_OK. See the :cpp:type:`mb_event_group_t` for more information about Modbus event masks.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
.. doxygenfunction:: mbc_slave_get_param_info
The function gets information about accessed parameters from modbus controller event queue. The KConfig 'CONFIG_FMB_CONTROLLER_NOTIFY_QUEUE_SIZE' key can be used to configure the notification queue size. The timeout parameter allows to specify timeout for waiting notification. The :cpp:type:`mb_param_info_t` structure contain information about accessed parameter.
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
Modbus serial master interface API overview
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
The Modbus master implementation requires parameter description table be defined before start of stack. This table describes characteristics (physical parameters like temperature, humidity, etc.) and links them to Modbus registers in specific slave device in the Modbus segment. The table has to be assigned to the modbus_controller interface using :cpp:func:`mbc_master_set_descriptor()` API call before start of communication.
Below are the interface API functions that are used to setup and use Modbus master stack from user application and can be executed in next order:
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
.. doxygenfunction:: mbc_master_set_descriptor
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
Assigns parameter description table for Modbus controller interface. The table has to be prepared by user according to particular
.. doxygenfunction:: mbc_master_send_request
This function sends data request as defined in parameter request, waits response from corresponded slave and returns status of command execution. This function provides a standard way for read/write access to Modbus devices in the network.
.. doxygenfunction:: mbc_master_get_cid_info
The function gets information about supported characteristic defined as cid. It will check if characteristic is supported and returns its description.
.. doxygenfunction:: mbc_master_get_parameter
The function reads data of characteristic defined in parameters from Modbus slave device and returns its data. The additional data for request is taken from parameter description table.
.. doxygenfunction:: mbc_master_set_parameter
The function writes characteristic's value defined as a name and cid parameter in corresponded slave device. The additional data for parameter request is taken from master parameter description table.
Application Example
-------------------
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
The examples below use the FreeModbus library port for slave and master implementation accordingly. The selection of stack is performed through KConfig menu "Selection of Modbus stack support mode" and related configuration keys.
:example:`protocols/modbus_slave`
freemodbus: Fix bug with incorrect coils read mask Contains two different component folders per each implementation (serial_master and serial_slave) with concrete ports. Added common public api for master and slave and common interface for master and slave implementation. Add support of cmake system (added cmake files). Added sdkconfig.defaults files for slave and master modbus examples. Updated make file and KConfig for freemodbus component Update according to review and fix doxygen warnings Fix Doxyfile to pass documentation build Update headers and change interface file names as per review comments Merge branch feature/freemodbus_move_rs485_mode_control Update after review: The stack modbus folder updated to support master and slave ports together and moved into freemodbus/modbus Stack and port files updated to remove duplicated simbols Make file, KConfig and CMakeLists.txt updated to compile master and slave stacks, common interface and concrete implementations of ports Stack callback functions execute callbacks using interface pointer from concrete port implementation User can instantiate any of concrete port using common API (only one concrete port at a time) and it does not require to select port by KConfig Port pins and mode configuration moved into example files from port files to allow user select pins and port mode (customer request) Changes tested using pymodbus, ModbusPoll and communication between two boards Updated DoxyFile according to public include path Fix maximum instance size for slave (merge from master of customer issue) Fix critical section issue TW#28622 (change spin lock based critical section to semaphore) Move serial port files into component port folder for master and slave accordingly Fix example issue showed in the log when IO slave is not configured correctly Fix conflicts while merging from origin/master Fix errors handling in modbus controller interface + some final corrections according to review Update maximum allowed number of slaves in the network segment Fix bug with incorrect coils read mask Closes https://github.com/espressif/esp-idf/issues/858
2018-10-19 13:51:27 +00:00
:example:`protocols/modbus_master`
Please refer to the specific example README.md for details.
Modbus Readme File
------------------
.. include:: ../../../../components/freemodbus/README.rst